Erratum
Green Star SA – Office V1.1 Technical Manual: IEQ-03, Page 2
Erratum Number
IEQ3-E-OFF1.1-1889
Guidance
2017-05-25
In Documentation Requirements; mechanically ventilated spaces; type 1); second bullet point:
Add “where CO2 levels exceed the limits indicated in Additional Guidance” to read:
“Be linked to an automated monitoring system (e.g. BMS) or equivalent to ensure continuous adjustment of the outside air rate where CO2 levels exceed the limits indicated in Additional Guidance”
Erratum
Mechanically ventilated spaces
Erratum Number
IEQ03-E-OB1-1558
In the Green Star SA - Office v1.1 Technical Manual, under ‘Credit Criteria’: replace Mechanically ventilated spaces first bullet point with the following:
• For 95% of the UA a carbon dioxide (CO2) monitoring and control system with a minimum of one CO2 sensor at all return points on each floor, is provided to facilitate continuous monitoring and adjustment of outside air ventilation rates to each level, to ensure independent control of ventilation rates to achieve outside air requirements;