Follow

IEQ-3 CARBON DIOXIDE MONITORING AND CONTROL

 

Technical Clarification

Application of SANS 10400-O

Technical Clarification Number
IEQ03-T-RC1-442

Guidance
2012-04-02

Wherever ‘SANS 10400-O’ is referred to within the IEQ-3 credit, this relates to SANS 10400-O:1990 for the purposes of Green Star SA – Retail Centre v1 rating tool. It is the project team’s responsibility to ensure however that the latest relevant building regulations are complied with for statutory purposes.”

 

Erratum

Application of SANS 10400-O

Erratum Number
IEQ03-E-RC1-442

Guidance
2012-04-02

On page 68 of the Green Star SA – Retail Centre v1 Technical Manual, under ‘Additional Guidance’:

- For the third-last bullet point on the page, delete “50% increase” and replace it with “11.25 l/s per person”
- For the second-last bullet point on the page, delete “100% increase” and replace it with “15 l/s per person”
- For the last bullet point on the page, delete “150% increase” and replace it with “18.75 l/s per person”

 

 

Was this article helpful?
0 out of 0 found this helpful
Have more questions? Submit a request

Comments