EMI-7 LIGHT POLLUTION

 

Technical Clarification

Alternative Documentation: Light Pollution Modelling Report

Technical Clarification Number
EMI7-T-MR1-0872

Guidance
2015-02-04

Where a Lighting Pollution Modelling Report is provided as part of a short report including:
• modelling results clearly demonstrating that all related areas and light fittings are included in the simulations
• and identify all areas area(s) that does not exceed the minimum requirements of CIBSE LG6 for illuminance levels

Then it is not required that the Tender drawing(s) and or As Built drawing(s) are marked up showing the area(s) that do not exceed the minimum requirements of CIBSE LG6 for illuminance levels. However the location and type of all external luminaires should still be marked up on the Tender drawing(s) and As Built drawing(s) to assist in demonstrating that all luminaires have been included in the modelling.

Note that this TC only applies to project teams that choose to demonstrate compliance with the credit criteria through modelling.

 

 