Technical Clarification
Definition of ‘extended period of time'
Erratum Number
IEQ-1-T-EBP1-2352
Guidance
2018-07-05
The GBCSA will accept the Interiors Tool description that ‘where a person is expected to work for a period longer than one continuous hour per day’ is equated in the EBP Technical Manual to ‘a space where a person is expected to work, or remain for an extended period of time’ and is a REGULARLY OCCUPIED SPACE.
The further definition/words in the Interiors Occupied Space (OS) don’t apply to the EBP Tool and the definitions with in the EBP Technical Manual as well the definitions within each credit should be taken into account when understanding and defining what REGULARLY OCCUPIED SPACE is for that specific credit.
-------------------------------------------------------------------------------------------------------------
Erratum
IAQ Manager
Erratum Number
IEQ-1-E-EBP1-2159
Guidance
2017-12-12
Project teams pursuing 1 point for IAQ Manager the following is required:
- Signed appointment letter of IAQ Manager
- Established IAQ Management Plan
- Perform an IAQ Baseline audit following I-BEAM templates (x3 PDF attachments scroll to the bottom of this list)
- Baseline Audit - Indoor Spaces (PDF)
- Baseline Audit - HVAC System (PDF)
- Baseline Audit - Exterior (PDF)
______________________________________________________
Erratum
IAQ manager appointment & duration
Erratum Number
IEQ-1-E-EBP1-2027
Guidance
2017-09-21
Amend the Credit Criteria for IAQ Manager to reflect the following sentence:
IAQ Manager 1 point is awarded where an IAQ manager is appointed for a minimum of 3 months during the performance period who supervises and manages the optimization of practices that prevent and minimize the build-up of indoor pollutants in buildings by implementing a IAQ Management Plan.
Whilst the project team does not have to demonstrate involvement of the appointed IAQ Manager for the full 12 months performance period - the project team is required to show that the IAQ Management Plan demonstrated evidence of:
o Assignment, Responsibilities and Training
o Establishing an Adequate IAQ Baseline
o Written Plans and Protocols
o Communications Programs
o Quality Assurance and Inspections
--------------------------------------------------------------------------------------------
Erratum
Indoor air quality testing
Erratum Number
IEQ-1-E-EBP1-1543
Guidance
2017-01-16
Under heading Indoor Air Quality Testing remove the word "annual" and replace it with "during performance period"
Reads The IAQ Manager shall conduct during the performance period indoor air quality testing, or arrange with a suitably qualified service provider to conduct indoor air quality testing using a calibrated device.
___________________________________________________________________________
Technical Clarification
CO Testing no Undercover parking garages
Erratum Number
IEQ-1-T-EBP1-1503
Guidance
2016-08-01
The project team is required to conduct indoor air quality testing of CO and CO2, to satisfy the requirements of this credit as the aim of the IEQ-1 credit is to monitor and control indoor pollutants.
However, projects cannot be penalised where parking garages are not present.
The CO testing may be made "Not Applicable" if the project does not contain any undercover parking garage(s).
Project team to submit a signed confirmation letter from the Building Owner confirming that there is no undercover parking garages in order to claim the CO Testing as Not Applicable.
----------------------------------------------------------------------------------------------
Erratum
Erratum Number
IEQ-1-E-EBP1-1177
Guidance
2016-01-21
Under heading documentation requirements: remove "7"
reads Corrective Action Plan, where required.
Sub-Heading remove word Ventilation add "Ventilated" reads: SYSTEM PERFORMANCE (NATURALLY VENTILATED SYSTEMS)
---------------------------------------------------------------------------------------------
Technical Clarification
Defining undercover parking areas for CO testing
TC Number
IEQ-1-TC-EBP1-1164
Guidance
2015-11-16
- The GBCSA provide clarification in this regard: CO levels must be tested in undercover parking areas (undercover is defined as fully enclosed or partially car parking areas). Parking decks ensuring good air quality through natural ventilation are encouraged.